Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T14CM02581
Parcel: 10408095C

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T14CM02581
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2014 MARTIN BROWN FIRE REVIEW Denied Please provide quantities of batteries to be stored on battery platform (type D rack). Provide anaylsis of hazardous material in batteries and how it conforms to Table 5003.1.1 of the 2012 International Fire Code.
05/23/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/29/2014 FERNE RODRIGUEZ OUT TO CUSTOMER Completed