Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T14CM02581
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/06/2014 | MARTIN BROWN | FIRE | REVIEW | Denied | Please provide quantities of batteries to be stored on battery platform (type D rack). Provide anaylsis of hazardous material in batteries and how it conforms to Table 5003.1.1 of the 2012 International Fire Code. |
| 05/23/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/29/2014 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |