Permit Number: T14CM02558
Parcel: 12404075A

Address:
1588 E 1ST ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM02558
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/13/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A1.0: PROVIDE ON THIS SHEET THE REQUIRED NUMBER OF PLUMBING FIXTURES PER THE IBC TABLE 2902.1, USING THE UPDATED OCCUPANT LOAD.
2. SHEET A1.0; CODE REVIEW (NUMBER OF EXITS): THE LOWER LEVEL INDICATES 3 EXITS ARE REQUIRED. REVISE PER THE IBC SECTION 1015.
3. SHEET A1.0; CODE REVIEW (OCCUPANCY SEPARATION): SECTION 302.3.3 IS REFERENCED FOR SEPARATION. REVISE THE CODE REFERENCE TO THE 2012 IBC.
4. SHEET A1.0; CODE REVIEW (OCCUPANT LOAD): TABLE 1003.2.2 IS REFERENCED FOR OCCUPANT LOAD. REVISE THE CODE REFERENCE TO THE 2012 IBC.
5. SHEET A1.0; CODE REVIEW (NUMBER OF EXITS): TABLE 1005.2.2 IS REFERENCED FOR THE NUMBER OF EXITS. REVISE THE CODE REFERENCE TO THE 2012 IBC.
6. SHEET A1.0; CODE REVIEW (EXIT TRAVEL DISTANCE): TABLE 1004.2.4 IS REFERENCED FOR EXIT TRAVEL DISTANCE. REVISE THE CODE REFERENCE TO THE 2012 IBC.
7. SHEET A3.0; KEYNOTES: NOTE 5 WAS NOT LOCATED ON THE ELEVATIONS. VERIFY.
8. SHEET S2.1; PLAN NOTES (15): IN NOTE 15, REFERENCE THE ARCHITECTURAL SHEET THAT INDICATES THE STRUCTURE SLOPE.
9. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/15/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Demonstrate energy code compliance for the addition to the building envelope using calculations based on the current code. Reference: Sections C101.4.3, C101.5, and C103.2, International Energy Conservation Code 2012.
2. Clarify the balancing notes for the existing fan coils (e.g. "Rebalance existing fan coil to3,000 CFM 975 CFM"?). Reference: Section 107.2.1, IBC 2012.
05/15/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide secondary (overflow) roof drainage for the new sun deck and porch roof. Reference: Sections 1101, 1106 and 1108, IPC 2012, and Sections 1611.1 and 1611.3, IBC 2012.
05/15/2014 ROBERT SHERRY WATER REVIEW Approved
05/15/2014 STEVE SHIELDS ZONING REVIEW Passed
05/20/2014 MARTIN BROWN FIRE REVIEW Approved
05/21/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
05/21/2014 LHANLY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed