Permit Number: T14CM02505
Parcel: 13409002J

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T14CM02505
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/11/2015 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
02/13/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The submitted load calculations show the proposed equipment has a total cooling capacity approximately 7.5-tons greater than the calculated total capacity. Similarly, the proposed equipment has a sensible capacity that is 9-tons greater than the calculated sensible cooling loads. Clarify the apparent discrepancy. [Initial comment: Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.]
02/13/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/17/2015 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Completed
02/24/2015 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Goodwill - 8358 E. Broadway Blvd
T14CM02505
Building Plan (3rd Review)

TRANSMITTAL DATE: February 24, 2015

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning has reviewed the building plans but cannot approve until the development package has been approved for the site changes

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
02/27/2015 JASON GREEN ENGINEERING REVIEW Reqs Change ENG will stamp the building plan approved upon approval of the DP Package DP14-0066.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/12/2015 SHANAE POWELL OUT TO CUSTOMER Completed
03/12/2015 CPIERCE1 REJECT SHELF Completed