Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T14CM02505
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/11/2015 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/13/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The submitted load calculations show the proposed equipment has a total cooling capacity approximately 7.5-tons greater than the calculated total capacity. Similarly, the proposed equipment has a sensible capacity that is 9-tons greater than the calculated sensible cooling loads. Clarify the apparent discrepancy. [Initial comment: Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.] |
| 02/13/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 02/17/2015 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 02/24/2015 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Goodwill - 8358 E. Broadway Blvd T14CM02505 Building Plan (3rd Review) TRANSMITTAL DATE: February 24, 2015 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning has reviewed the building plans but cannot approve until the development package has been approved for the site changes 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 02/27/2015 | JASON GREEN | ENGINEERING | REVIEW | Reqs Change | ENG will stamp the building plan approved upon approval of the DP Package DP14-0066. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/12/2015 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
| 03/12/2015 | CPIERCE1 | REJECT SHELF | Completed |