Permit Number: T14CM02505
Parcel: 13409002J

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T14CM02505
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/03/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change SHEET TS1
1. Your occupancy load calculation needs to be further refined into the actual use catagories of mercantile as per table 1004.1.2: grade floor areas 1/30, Storage stock and shipping areas 1/300.
a. Once a new occupancy load has been calculated confirm number of toilet fixtures required and exits required. Modify drawings as required.
2. The gross area shown on TS1 is 100 square feet larger than the areas shown on sheet A1. Is the loading dock 365 s.f. or 265 s.f. Please reconcile.
SHEET A1
3. The curb ramp west of the new facade is not code compliant. Reference ICC A117.1, Section 406.
4. Door 108 needs clearances as required by 404.2.3.2 with a latch and a closer.
END OF REVIEW
12/10/2014 JASON GREEN ENGINEERING REVIEW Reqs Change ENG can not approve the building plan until the develoment plan package DP14-0066 has been approved and verification that the buildig plan matches the site plan with associated conditions.

Once the DPP is approved ENG can approve the building plan over the counter upon verification that it matches the DP Package. JG
12/11/2014 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Goodwill - 8358 E. Broadway Blvd
T14CM02505
Building Plan (1st Review)

TRANSMITTAL DATE: December 11, 2014

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning has reviewed the building plans but cannot approve until a development package has been submitted and approved for the site changes

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
12/19/2014 ROBERT SHERRY WATER REVIEW Completed
12/19/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide the rim elevation of the next upstream sanitary manhole and the first floor elevation. Determine the need for a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson.
12/22/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.
12/24/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Reqs Change T14CM02505

1. Electrical floor plan: provide emergency powered lighting at both interior and exterior for all exit discharge doorways, IBC 1006.3.5.

2. Single line diagram of service: clarify the location of panel 'A'.

3. Panel schedule information: show an appropriate AIC rating for panel 'A', NEC 110.22.

4. City of Tucson Outdoor Lighting Code (Ord #10963) compliance: show the rated color temperature of proposed fixtures as not exceeding 3500K, Section 402. Notate plans, or provide manufacturer spec sheet with color temperature rating.

Ken Van Karsen
Electrical Plan Review
PDSD, City of Tucson
520-837-4906
Kenneth.VanKarsen@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
02/05/2015 SHANAE POWELL OUT TO CUSTOMER Completed
02/05/2015 CPIERCE1 REJECT SHELF Completed