Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T14CM02505
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/03/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | SHEET TS1 1. Your occupancy load calculation needs to be further refined into the actual use catagories of mercantile as per table 1004.1.2: grade floor areas 1/30, Storage stock and shipping areas 1/300. a. Once a new occupancy load has been calculated confirm number of toilet fixtures required and exits required. Modify drawings as required. 2. The gross area shown on TS1 is 100 square feet larger than the areas shown on sheet A1. Is the loading dock 365 s.f. or 265 s.f. Please reconcile. SHEET A1 3. The curb ramp west of the new facade is not code compliant. Reference ICC A117.1, Section 406. 4. Door 108 needs clearances as required by 404.2.3.2 with a latch and a closer. END OF REVIEW |
12/10/2014 | JASON GREEN | ENGINEERING | REVIEW | Reqs Change | ENG can not approve the building plan until the develoment plan package DP14-0066 has been approved and verification that the buildig plan matches the site plan with associated conditions. Once the DPP is approved ENG can approve the building plan over the counter upon verification that it matches the DP Package. JG |
12/11/2014 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Goodwill - 8358 E. Broadway Blvd T14CM02505 Building Plan (1st Review) TRANSMITTAL DATE: December 11, 2014 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning has reviewed the building plans but cannot approve until a development package has been submitted and approved for the site changes 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
12/19/2014 | ROBERT SHERRY | WATER | REVIEW | Completed | |
12/19/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide the rim elevation of the next upstream sanitary manhole and the first floor elevation. Determine the need for a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson. |
12/22/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012. |
12/24/2014 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | T14CM02505 1. Electrical floor plan: provide emergency powered lighting at both interior and exterior for all exit discharge doorways, IBC 1006.3.5. 2. Single line diagram of service: clarify the location of panel 'A'. 3. Panel schedule information: show an appropriate AIC rating for panel 'A', NEC 110.22. 4. City of Tucson Outdoor Lighting Code (Ord #10963) compliance: show the rated color temperature of proposed fixtures as not exceeding 3500K, Section 402. Notate plans, or provide manufacturer spec sheet with color temperature rating. Ken Van Karsen Electrical Plan Review PDSD, City of Tucson 520-837-4906 Kenneth.VanKarsen@tucsonaz.gov |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/05/2015 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
02/05/2015 | CPIERCE1 | REJECT SHELF | Completed |