Review Details: WALK THRU - COMM
Permit Number - T14CM02462
Review Name: WALK THRU - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/12/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Verify that the surface temperature of the exhaust duct is less that 120 degrees Fahrenheit. Reference: Section 604.2, IMC 2012. 2. Provide the manufacturer's installation instructions for the two cure ovens to clarify how the duct is to be connected to the ovens and what the air flow is supposed to be. Reference: Sections 501, 502, and 503, IFGC 2012. 3. Indicate the termination points for the pressure regulator vents. |