Review Date Reviewer's Name Type of Review Description Status Comments
04/29/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide descriptions of the three appliances being connected to gas service.
2. Clarify the gas requirements of each appliance, e.g. inlet pressure regulation, multiple gas input points, and termination of the regulator vents.
3. According to Table 402.4(5), IFGC 2012, at a developed length of 300 feet and a 1 PSI pressure drop, a 2" schedule 40 metallic pipe has a capacity of 5,600 CFH, not 5,882 CFH.
4. With all of this gas being sent to these three appliances, how are the products of combustion being eliminated from the building?