Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T14CM02442
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2014 MICHAEL ST. PAUL ZONING REVIEW Denied P&DS TRANSMITTAL


FROM: Michael St.Paul, Planning Technician

PROJECT:
T14CM02442
1541 East 10th Street
Two-addition to SFR


TRANSMITTAL: April 28, 2014


COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).


This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, .9 & .10.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). The height of the proposed two-story addition is twenty (20) feet along the north and east property lines. The required setback is thirteen feet four inches (13'-4") to both property lines. The propose setback to the north and east property lines is one (1) foot for each setback.
06/09/2014 CPIERCE1 ENGINEERING REVIEW Needs Review
06/09/2014 CPIERCE1 NPPO REVIEW Needs Review
06/09/2014 CPIERCE1 BUILDING-RESIDENTIAL REVIEW Needs Review