Permit Number: T14CM02427
Parcel: 113080450

Address:
2922 N MITCH DR

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T14CM02427
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2014 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T14CM02427
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide revised plans and calculations, highlighting any changes or with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

ELEVATIONS:

1. Clarify the window size for bedroom #1 shown on the Rear Elevation sheet #2, R301.1. The floor plan shows an appropriate egress window size, and the elevation is undersized.

NOTES:

1. Show fiber-cement board or glass mat gypsum backers for tiled walls in tub and shower areas, R702.4.2.

PLUMBING PLANS:

1. Limit all code references to those recognized by the City of Tucson, 2012 IRC. Update note #10.
2. Clarify the master bath water closet 2" vent (VTR) size on the plan consistent with the 3" size shown on the isometric.

MECHANICAL PLANS:

1. Show supply ducts with minimum R-8 insulation except when completely located inside the thermal envelope, N1103.2.1. Clarify note #1 adding the words "thermal envelope".
2. Show the kitchen exhaust fan with minimum 100 CFM rating, M1507.3.

ELECTRICAL PLANS:

1. Limit all code references to those recognized by the City of Tucson, 2012 IRC. Update the three 2006 references shown on the Panel Diagram.
2. Revise the electrical load calculations for sizing the dwelling electrical load. Update the 19,744 total load entry.
3. Show a receptacle outlet within 3' of each lavatory basin in each bathroom, E3901.6. Add a receptacle in bath #2.

OUTDOOR LIGHTING CODE

1. Show the proposed fixtures as full cut-off FCO style, or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing is U=0.40, N1102.1. Show the "U" factors of the proposed windows on the plans.
2. The simplified prescribed energy values for mass walls is R=6 when applied on the interior side, N1102.1. Show the "R" value of required furr-out wall insulation for proposed living space on the plans.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/15/2014 CPIERCE1 OUT TO CUSTOMER Completed