Permit Number: T14CM02408
Parcel: 13632006F

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM02408
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/10/2014 KEN BROUILLETTE FIRE REVIEW Denied Please indicate on site plan the location of the nearest fire hydrant. The required fire flow is 2,250 GPM for 2hrs duration at 20 psi residual pressure. A fire hydrant shall be within 600 feet of all portions of the new structure.
Indicate that the fire access to the structure is a minimum of 20 feet wide, less than 10 percent in grade, and the location of the approved fire department turnaround per Appendix D of the 2012 International Fire Code.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/15/2014 GERARDO BONILLA APPROVAL SHELF Completed
07/15/2014 GERARDO BONILLA OUT TO CUSTOMER Completed
07/15/2014 CPIERCE1 REJECT SHELF Completed