Permit Review Detail
Review Status: Completed
Review Details: PLANS OK TO SUBMIT - COMM
Permit Number - T14CM02405
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/28/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Condensate drains shall not terminate at a vent (keynote 10/M101). Reference: Section 901.4, IPC 2012. |
| 04/28/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Condensate drains shall not terminate at a vent (keynote 10/M101). Reference: Section 901.4, IPC 2012. 2. Clarify the termination of the condensate drain for FCU-1 (i.e. does it terminate in a location that will not result in surface flow?). Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson. |
| 04/30/2014 | AROMERO4 | FIRE | REVIEW | Needs Review | |
| 04/30/2014 | AROMERO4 | ADA | REVIEW | Needs Review | |
| 04/30/2014 | AROMERO4 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 04/30/2014 | AROMERO4 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 04/30/2014 | AROMERO4 | ENGINEERING | REVIEW | Needs Review | |
| 04/30/2014 | AROMERO4 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 04/30/2014 | DAVID RIVERA | ZONING | REVIEW | Passed |