Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T14CM02405
Parcel: 10603148A

Address:
125 W YAVAPAI RD

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - COMM

Permit Number - T14CM02405
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Condensate drains shall not terminate at a vent (keynote 10/M101). Reference: Section 901.4, IPC 2012.
04/28/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Condensate drains shall not terminate at a vent (keynote 10/M101). Reference: Section 901.4, IPC 2012.
2. Clarify the termination of the condensate drain for FCU-1 (i.e. does it terminate in a location that will not result in surface flow?). Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson.
04/30/2014 AROMERO4 FIRE REVIEW Needs Review
04/30/2014 AROMERO4 ADA REVIEW Needs Review
04/30/2014 AROMERO4 BUILDING-COMMERCIAL REVIEW Needs Review
04/30/2014 AROMERO4 ELECTRICAL-COMMERCIAL REVIEW Needs Review
04/30/2014 AROMERO4 ENGINEERING REVIEW Needs Review
04/30/2014 AROMERO4 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
04/30/2014 DAVID RIVERA ZONING REVIEW Passed