Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM02403
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/29/2014 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
04/29/2014 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
04/30/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
04/30/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
04/30/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
04/30/2014 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
05/01/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Relocation of an existing thermostat constututes an alteration of an existing HVAC system. Verify that the thermostat complies with the requirements of Section C403.2.4.1, IECC 2012. Reference: Section C101.4.3, IECC 2012. 2. Provide a means of differentiating between the four existing heat pumps (i.e. don't call them all "HP-X"). |
05/01/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
05/01/2014 | ROBERT SHERRY | WATER | REVIEW | Approved | |
05/02/2014 | FRODRIG2 | WWM | REVIEW | Passed |