Permit Number: T14CM02322
Parcel: 10409002D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM02322
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2014 CPIERCE1 BUILDING-COMMERCIAL REVIEW Needs Review
04/28/2014 CPIERCE1 FIRE REVIEW Needs Review
05/05/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Reqs Change Plan review has been completed and the following corrections are required. Please provide a written response to comments with plan re-submittal.

1) Interlock of EF1 & EF2 to occupancy sensor does not provide for correct sequencing of operation with supply air from RTU 3. Fans may be on 24/7 timer set to operate whenever building is occupied, or they may be interlocked with RTU. Ref: IMC 403.2.1(4)


If there are questions regarding this review contact:

LeeRay
520-837-4906
LeeRay.Hanly@tucsonaz.gov
05/06/2014 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Reqs Change Plan review has been completed and the following corrections are required. Please provide a written response to comments with plan re-submittal.

1) Show all wco's on dwv isometric plan. Ref IBC 107.2.1
2) Clarify note in Water Calculations referencing 7-5 of UPC and ΒΌ" /ft slope on service line. Ref: IBC 107.2.1
3) Provide cut-sheets indicating chemical dispenser at mop sink has internal back flow prevention, or specify adequate backflow protection.



If there are questions regarding this review contact:

LeeRay
520-837-4906
LeeRay.Hanly@tucsonaz.gov
05/06/2014 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Reqs Change Plan review has been completed and the following corrections are required. Please provide a written response to comments with plan re-submittal.

1) Provide sequence of operation for restroom exhaust fans so that not more than 10% of supply air to these spaces is recirculated. Ref: IMC 403.2.1(4).
2) Return air notes indicate full 2000 cfm at registers. Coordinate return air at registers with required outside air for final balancing of equipment in field. Ref: IBC 107.2.1
3) Specify duct insulation in keynote 8 pp M1. Ref: IBC 107.2.1





If there are questions regarding this review contact:

LeeRay
520-837-4906
LeeRay.Hanly@tucsonaz.gov