Permit Number: T14CM02322
Parcel: 10409002D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM02322
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/23/2014 DAVID RIVERA ZONING REVIEW Approved
04/23/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
04/23/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
04/23/2014 ROBERT SHERRY WATER REVIEW Approved
04/23/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change 1. Egress exits not compliant with 2012 IBC, Section 1015.2.1, separation distance.
Certail details through out drawings have too light of line weight, reference A/A4. Can't see fixtures and clearances. Other sheets have same problem. Reconcile and resubmit.
3. Provide structural calculations for the following:
a. All new roof top mounted HVAC equipment.
b. Wall mounted water heater including partition analysis.
END OF REVIEW
04/23/2014 JASON GREEN ENGINEERING REVIEW Approved
04/23/2014 MARTIN BROWN FIRE REVIEW Denied Code review indicates NO fire sprinklers. This building does (or will) have sprinklers. Please revise cover sheet and indicate sprinkler work will be a deferred submittal.
04/23/2014 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
04/28/2014 CPIERCE1 WWM REVIEW Passed
04/28/2014 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review