Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM02322
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/23/2014 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 04/23/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 04/23/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 04/23/2014 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/23/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Egress exits not compliant with 2012 IBC, Section 1015.2.1, separation distance. Certail details through out drawings have too light of line weight, reference A/A4. Can't see fixtures and clearances. Other sheets have same problem. Reconcile and resubmit. 3. Provide structural calculations for the following: a. All new roof top mounted HVAC equipment. b. Wall mounted water heater including partition analysis. END OF REVIEW |
| 04/23/2014 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 04/23/2014 | MARTIN BROWN | FIRE | REVIEW | Denied | Code review indicates NO fire sprinklers. This building does (or will) have sprinklers. Please revise cover sheet and indicate sprinkler work will be a deferred submittal. |
| 04/23/2014 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 04/28/2014 | CPIERCE1 | WWM | REVIEW | Passed | |
| 04/28/2014 | CPIERCE1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |