Permit Number: T14CM02300
Parcel: 13817047B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM02300
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/12/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
06/13/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. [Initial comment: Submit documentation from the Pima County Department of Environmental Quality showing that the proposed gray water collection system has been approved for construction under a General Permit for the collection and use of gray water by a non-residential entity producing in excess of 400 Gallons per day. Reference: Section R18-9-17, Arizona Administrative Code.]
2. Comment not addressed. [Initial comment: Provide roof drainage calculations based on the 100-year hourly rainfall rate for Tucson, 3" per hour. Show the dimensions of the gutters. Reference: Sections 1106.1 and1106.6, IPC 2012.]
06/13/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide the revised COMcheck envelope compliance certificate. [Initial comment: The COMcheck envelope compliance certification calls for the metal building roof to have a double layer of insulation with R-38 in the cavity, R-3.5 thermal blocks, and continuous R-8 insulation. Provide shop drawings to show how this level of insulation is to be accomplished.]
2. Provide the revised COMcheck envelope compliance certificate. [Initial comment: Revise the COMcheck envelope compliance certification to include the exterior doors for the building. Show the door properties (e.g. U-values and, in the case of doors with more than 50% glazing, the SHGF) on the drawings.]

Final Status

Task End Date Reviewer's Name Type of Review Description
06/19/2014 CPIERCE1 REJECT SHELF Completed
06/16/2014 SHANAE POWELL OUT TO CUSTOMER Completed