Permit Number: T14CM02294
Parcel: 11305057B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM02294
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/15/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The water supply to coffee and other non-carbonated beverage dispensers shall be protected by dual check backflow preventers that conform to ASSE 1022, not ASSE 1024. Reference: Section 606.16.10, IPC 2012. [Initial comment: Clarify the type of backflow preventer to be used with the appliances that are directly-connected to domestic water; the Watts model 009 is a reduced pressure principle backflow assembly (ASSE 1013), not a dual check valve (ASSE 1022). Specify the devices to be used for the appliance connections. Reference: Sections 608.1 and 608.15, IPC 2012.]