| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/15/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The water supply to coffee and other non-carbonated beverage dispensers shall be protected by dual check backflow preventers that conform to ASSE 1022, not ASSE 1024. Reference: Section 606.16.10, IPC 2012. [Initial comment: Clarify the type of backflow preventer to be used with the appliances that are directly-connected to domestic water; the Watts model 009 is a reduced pressure principle backflow assembly (ASSE 1013), not a dual check valve (ASSE 1022). Specify the devices to be used for the appliance connections. Reference: Sections 608.1 and 608.15, IPC 2012.] |