Permit Number: T14CM02253
Parcel: 112033930

Review Status: Active

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T14CM02253
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2014 ANY ENGINEERING REVIEW Active
04/21/2014 ANY BUILDING-RESIDENTIAL REVIEW Active
04/29/2014 STEVE SHIELDS ZONING REVIEW Denied P&DS TRANSMITTAL


FROM: Steve Shields, Lead Planner

PROJECT:
2818 E. Greenlee Street
T14CM02253
Attached Carport


TRANSMITTAL: April 29, 2014


COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).


This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A).

Based on a wall height of 12'-5" the required perimeter yard setback from the proposed attached carport to the west property line is 8'-4" proposed perimeter yard setback is
3'-0".
04/29/2014 SSHIELD1 NPPO REVIEW Passed