Permit Number: T14CM02186
Parcel: 13414018N

Address:
7501 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM02186
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/29/2014 MARTIN BROWN FIRE REVIEW Denied Could not find requested information from first submittal.KRB
05/07/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET S2.0; GENERAL STRUCTURAL NOTES (STRUCTURAL STEEL): NO NOTE IS INCLUDED FOR PIPES. ARE PIPES BEING USED (PER PAGE 5 OF THE CALCULATIONS)?
2. SHEETS S2.0 AND S5.0; STRUCTURAL CALCULATIONS (PAGE 1): THE CALCULATIONS (PAGE 1) INDICATE WELDING ON THIS PRPOJECT, BUT THE DETAILS ON SHEET S5.0 SHOW NO WELDING. CLARIFY.
3. SHEET S5.0 (TABLE 1); STRUCTURAL CALCULATIONS: CALCULATIONS ARE NOT INCLUDED FOR THE VARIOUS COLUMN SIZES SHOWN ON THE DRAWINGS (SPECIFICALLY COLUMNS 2, 3, 4, AND 5). PROVIDE.
4. SHEET S5.0; PLAN NOTES: NOTE 6 WAS NOT LOCATED ON THE PLAN OR THE CONNECTION DETAIL. VERIFY.
5. STRUCTURAL CALCULATIONS (PAGES 5 AND 31 THROUGH 33); SHEET S5.0: PAGE 5 OF THE CALCULATIONS INDICATES COLUMN SECTIONS ARE PIPE 6.0, A53 GRADE B (35 KSI YIELD STRESS), WHILE CALCULATION PAGES 31 THROUGH 33 INDICATE HSS6X6X1/4 (46 KSI YIELD STRESS). SHEET S5.0 INDICATES VARIOUS COLUMN SIZES IN TABLE 1 (ALL TUBES). CLARIFY.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/09/2014 CPIERCE1 REJECT SHELF Completed