Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T14CM02186
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/29/2014 | MARTIN BROWN | FIRE | REVIEW | Denied | Could not find requested information from first submittal.KRB |
| 05/07/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET S2.0; GENERAL STRUCTURAL NOTES (STRUCTURAL STEEL): NO NOTE IS INCLUDED FOR PIPES. ARE PIPES BEING USED (PER PAGE 5 OF THE CALCULATIONS)? 2. SHEETS S2.0 AND S5.0; STRUCTURAL CALCULATIONS (PAGE 1): THE CALCULATIONS (PAGE 1) INDICATE WELDING ON THIS PRPOJECT, BUT THE DETAILS ON SHEET S5.0 SHOW NO WELDING. CLARIFY. 3. SHEET S5.0 (TABLE 1); STRUCTURAL CALCULATIONS: CALCULATIONS ARE NOT INCLUDED FOR THE VARIOUS COLUMN SIZES SHOWN ON THE DRAWINGS (SPECIFICALLY COLUMNS 2, 3, 4, AND 5). PROVIDE. 4. SHEET S5.0; PLAN NOTES: NOTE 6 WAS NOT LOCATED ON THE PLAN OR THE CONNECTION DETAIL. VERIFY. 5. STRUCTURAL CALCULATIONS (PAGES 5 AND 31 THROUGH 33); SHEET S5.0: PAGE 5 OF THE CALCULATIONS INDICATES COLUMN SECTIONS ARE PIPE 6.0, A53 GRADE B (35 KSI YIELD STRESS), WHILE CALCULATION PAGES 31 THROUGH 33 INDICATE HSS6X6X1/4 (46 KSI YIELD STRESS). SHEET S5.0 INDICATES VARIOUS COLUMN SIZES IN TABLE 1 (ALL TUBES). CLARIFY. 6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/09/2014 | CPIERCE1 | REJECT SHELF | Completed |