04/29/2014 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Completed T14CM02105

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

1. Provide Manual J/S/D calculations in accordance with M1401.3, M1601.1. Systems shall be sized in accordance with Manual S based on building loads calculated in accordance with Manual J and duct systems sized in accordance with Manual D.

2. Provide an electrical load calculation to verify sufficient capacity of existing 100 amp electrical service, E3602.2.