Review Date Reviewer's Name Type of Review Description Status Comments
04/16/2014 MARTIN BROWN FIRE REVIEW Approved
04/24/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A0.0; SITE INFORMATION/OCCUPANCY: A NOTE UNDER THE TOTAL OCCUPANT LOAD INDICATES THAT LOAD (70) DOES NOT INCLUDE THE OUTSIDE DINING AREA. THE TOTAL OCCUPANT LOAD FOR THE BUILDING MUST INCLUDE THE OUTSIDE DINING. REVISE.
2. SHEET A1.1; WALL TYPE LEGEND: WALL TYPES 3B, 4, AND 8 WERE NOT LOCATED ON THE PLAN. VERIFY.
3. SHEET A1.1; WALL TYPE LEGEND: PROVIDE A DETAIL ON THE DRAWINGS FOR THE METAL STUD REINFORCEMENT INDICATED IN WALL TYPES 2 AND 3A. INDICATE THE BRACING SIZE AND SPACING, AND INCLUDE CONNECTOR SIZE AND QUANTITY AT THE TOP OF THE WALL AND AT THE STRUCTURE ABOVE.
4. SHEETS A4.0 THROUGH A4.3; KEY NOTES: NOTES 2, 10, 11, 12, 13, 23, 29, 30, 33, 43, AND 45 WERE NOT LOCATED ON THE ELEVATIONS. VERIFY.
5. SHEET A4.4; KEY NOTES: NOTE 13 WAS NOT LOCATED ON THE ELEVATIONS. VERIFY.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
04/25/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
05/01/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Keynote #13 on sheet P2.0 calls for the water heater to be wall-mounted. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Section 301.2, IPC 2012.
2. Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle (note: item #P608 is not shown on the plumbing schedule). Reference: Section 416.6, IPC 2012, as amended by the City of Tucson.
3. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.
4. Appliances (e.g. soda dispensers, ice makers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012.
5. Water supply connections to beverage dispensers shall be protected with backflow preventers conforming to ASSE 1022 (the Wilkins 700 dual check backflow preventer conforms to ASSE 1024). Reference: Section 608.16.1, IPC 2012.
6. Provide the manufacturer's safety data sheet (MSDS) for the aluminum chloride contained in the chemical dispenser solution. Justify the use of a double check valve assembly for backflow protection. Reference: Section 608.13.9, IPC 2012.
05/01/2014 ROBERT SHERRY WATER REVIEW Approved
05/02/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Under which permit has the building owner installed the air handlers? Reference: Section 107.2.1, IBC 2012.
2. Clarify the intent of note #3 on the indoor air handling schedule (M3.0) as compared to the fan operation note in the thermostat setup instructions on sheet M1.0. Reference: Section 107.2.1, IBC 2012 and Section 403.3, IMC 2012.
05/09/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Reqs Change Plan review has been completed and the following corrections are required. Please provide a written response to comments with plan re-submittal.

1) Errata: Circuits LP-15, RP-23, RP-25 not located in lighting or power plans.
2) Provide information to show IECC interior lighting compliance. ComCheck is ok for this purpose
3) EF-2 in the "Electric Connection Schedule" has notation to connect to restroom lighting circuit, coordinate connections with panel schedule entries. Also clarify sequence of operation so that AHU-1 never recirculates more than 10% of the supply air in restrooms to the occupied area of the restaurant. 24/7 time switches set to operate EF2 whenever restaurant is occupied work well for this.


If there are questions regarding this review contact:

LeeRay
520-837-4906
LeeRay.Hanly@tucsonaz.gov

Final Status