Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/21/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
05/21/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Clarify source of the occupant load used to determine the amount of outside air for the building. Section C403.2.5, IECC 2012 requires the HVAC system to have the capability to reduce the amount of ventilation to the minimum ventilation calculated by Section 403.3, IMC 2012. [Initial comment: Provide calculations demonstrating adequate ventilation using the current code. The calculations for rooftop units supplying multiple zones shall comply with Sections403.3.2.3, IMC 2012. Reference: Section 403.2, IMC 2012.] |
05/21/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |