Permit Number: T14CM01967
Parcel: 101235160

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T14CM01967
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/21/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/21/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Clarify source of the occupant load used to determine the amount of outside air for the building. Section C403.2.5, IECC 2012 requires the HVAC system to have the capability to reduce the amount of ventilation to the minimum ventilation calculated by Section 403.3, IMC 2012. [Initial comment: Provide calculations demonstrating adequate ventilation using the current code. The calculations for rooftop units supplying multiple zones shall comply with Sections403.3.2.3, IMC 2012. Reference: Section 403.2, IMC 2012.]
05/21/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved