Permit Number: T14CM01963
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM01963
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2014 DAVID RIVERA ZONING REVIEW Approved
04/08/2014 LOREN MAKUS ENGINEERING REVIEW Approved
04/08/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET G1.0; CODE INFORMATION: REVISE THE NEC TO THE 2011 EDITION.
2. SHEET D1.0; DEMOLITION KEY NOTES: NOTE 5 WAS NOT LOCATED ON THE PLAN. VERIFY.
3. SHEET A5.2; CASHWRAP: THE IBC SECTION 1109.12.2 PLACES ACCESSIBILITY REQUIREMENTS AT THE CHECK-OUT COUNTER. PROVIDE AN ACCESSIBLE PORTION AT THE COUNTER TO MEET THAT REQUIREMENT.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
04/08/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/09/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/09/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
04/09/2014 ROBERT SHERRY WATER REVIEW Approved
04/09/2014 MARTIN BROWN FIRE REVIEW Approved Top of storage cannot exceed 12'-0" above finished floor without showing revised sprinkler hydraulic calculations.
04/09/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/18/2014 CPIERCE1 WWM REVIEW Passed