Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM01963
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/08/2014 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 04/08/2014 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 04/08/2014 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 04/08/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET G1.0; CODE INFORMATION: REVISE THE NEC TO THE 2011 EDITION. 2. SHEET D1.0; DEMOLITION KEY NOTES: NOTE 5 WAS NOT LOCATED ON THE PLAN. VERIFY. 3. SHEET A5.2; CASHWRAP: THE IBC SECTION 1109.12.2 PLACES ACCESSIBILITY REQUIREMENTS AT THE CHECK-OUT COUNTER. PROVIDE AN ACCESSIBLE PORTION AT THE COUNTER TO MEET THAT REQUIREMENT. 4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 04/09/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 04/09/2014 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/09/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 04/09/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | Top of storage cannot exceed 12'-0" above finished floor without showing revised sprinkler hydraulic calculations. |
| 04/09/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 04/18/2014 | CPIERCE1 | WWM | REVIEW | Passed |