Permit Number: T14CM01932
Parcel: 118262100

Address:
701 E 36TH ST

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T14CM01932
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/07/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A1.0; FLOOR PLAN: THE NEW CMU WALL (NOTE 7) MUST INDICATE WALL REINFORCING, NEW LINTEL OVER THE OPENING, NEW ROOF, AND NEW FOOTINGS AS REQUIRED. PROVIDE DESIGN AS NEEDED.
2. SHEET A1.0; FLOOR PLAN: IS THIS NEW RESTROOM ACCESSIBLE? VERIFY.
3. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/07/2014 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 701 E. 36th Street
T14CM01932
Building Plan (Revision)

TRANSMITTAL DATE: May 7, 2014

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. As a building expansion is proposed a revised development package is required.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the revised approved development package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
05/08/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Correct the calculations in the fixture connecetion schedule and the pressure loss calculations.
2. Verify that the water demand can be accommodated by the existing water meter.
3. Show that the minimum plumbing ffixtures have been provided (e.g. drinking fountain).
4. Verify with the manufacturer that the specified water heaters can successfully supply hot water to the lavatories.
5. Provide power for the second water heater.
05/08/2014 CPIERCE1 FIRE REVIEW Needs Review
05/08/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show that the building addition complies to the requirements of the 2012 IECC
05/08/2014 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/08/2014 CPIERCE1 APPROVAL SHELF Completed
05/08/2014 CPIERCE1 OUT TO CUSTOMER Completed