Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM01932
Parcel: 118262100

Address:
701 E 36TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM01932
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/07/2014 STEVE SHIELDS ZONING REVIEW Approved
04/07/2014 JASON GREEN ENGINEERING REVIEW Approved
04/07/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A1.0: PROVIDE AN ENLARGED PLAN OF THE NEW RESTROOM. THE RESTROOM MUST MEET ALL ACCESSIBILITY ISSUES, INCLUDING SPACE REQUIREMENTS, GRAB BARS, ETC.
2. GENERAL: PROVIDE WRITTEN RESPONSE TO THE REVIEW COMMENT.
04/07/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/08/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The building shell being modified in this activity does not appear to have been conditioned. Section C101.4.5, IECC 2012 requires the space to be brought into full compliance with the current energy code. Provide energy code compliance calculations for the building envelope, the mechanical system, and the internal lighting. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2012.
2. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.
04/08/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Reqs Change
04/08/2014 ROBERT SHERRY WATER REVIEW Denied Verify that backflow protection has been provided at the water meter.
04/08/2014 KEN BROUILLETTE FIRE REVIEW Approved
04/08/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Reference: Section 107.2.1, IBC 2012.
04/15/2014 FRODRIG2 WWM REVIEW Passed