Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM01931
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/15/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The HVAC load calculations do not support the installation of two 3-ton heat pumps for this building. 2. The mechanical specifications do not indicate the SEER for the two heat pumps. Verify that the specified unitary heat pumps comply with the requirements of Table C406.2 (2). Reference: Section C406.2, IECC 2012. 3. Provide the documentation for the roof U-value shown on COMcheck. Input the correct U-value for the calculations. |
04/15/2014 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/16/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. PREVIOUS COMMENT 1: THERE ARE STILL FOUR EXIT SIGNS AT THE SLIDING DOORS, BUT THAT IS NOT THE MAIN ISSUE. EACH SLIDING DOOR MUST MEET THE CRITERIA SPECIFIED IN THE IBC SECTION 1008.1.4.3. ON THE DRAWINGS, PROVIDE A SPECIFICATION/NOTES FOR THE SLIDING DOORS, ADDRESSING EACH ITEM IN THAT CODE SECTION. 2. PREVIOUS COMMENT 3: THE PARTITION DETAIL ON A4.0 STILL SHOWS NO BRACING TO THE TOP OF THE WALL, LISTING THE BRACE SIZE AND SPACING, AND THE CONNECTION OF THE BRACE TO THE TOP OF THE PARTITION AND TO THE STRUCTURE ABOVE. |
04/16/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed |