Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14CM01931
Parcel: 118262100

Address:
701 E 36TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM01931
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/15/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The HVAC load calculations do not support the installation of two 3-ton heat pumps for this building.
2. The mechanical specifications do not indicate the SEER for the two heat pumps. Verify that the specified unitary heat pumps comply with the requirements of Table C406.2 (2). Reference: Section C406.2, IECC 2012.
3. Provide the documentation for the roof U-value shown on COMcheck. Input the correct U-value for the calculations.
04/15/2014 ROBERT SHERRY WATER REVIEW Approved
04/16/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT 1: THERE ARE STILL FOUR EXIT SIGNS AT THE SLIDING DOORS, BUT THAT IS NOT THE MAIN ISSUE. EACH SLIDING DOOR MUST MEET THE CRITERIA SPECIFIED IN THE IBC SECTION 1008.1.4.3. ON THE DRAWINGS, PROVIDE A SPECIFICATION/NOTES FOR THE SLIDING DOORS, ADDRESSING EACH ITEM IN THAT CODE SECTION.
2. PREVIOUS COMMENT 3: THE PARTITION DETAIL ON A4.0 STILL SHOWS NO BRACING TO THE TOP OF THE WALL, LISTING THE BRACE SIZE AND SPACING, AND THE CONNECTION OF THE BRACE TO THE TOP OF THE PARTITION AND TO THE STRUCTURE ABOVE.
04/16/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed