Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T14CM01923
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/08/2014 | KEN BROUILLETTE | FIRE | REVIEW | Denied | 1. COVER SHEET LIST THE TYPE OF CONSTRUCTION AS VB AND LIST THE BASE SQUARE FOOTAGE FOR TABLE 503 IS 17,500 SQUARE FEET. PLEASE EXPLAIN. 2. INDICATE HOW COMPLIANCE WITH SECTION 910 SMOKE AND HEAT REMOVAL IS SATISFIED OR CHAPTER 32 OF THE IFC IF HIGH PILED STORAGE OCCURING. 3. THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE A WET SYSTEM, UNLESS THIS BUILDING IS SUBJECT TO FREEZING TEMPERATURES. PLEASE EXPLAIN |
| 04/08/2014 | JASON GREEN | ENGINEERING | REVIEW | Reqs Change | DATE: April 8, 2014 REVIEWER: Jason Green, CFM ACTIVITY: T14CM01923 (Building Plan) SUMMARY: Engineering Division of Planning & Development Services Department has received the building plan (T14CM01923). Engineering Division does not recommend approval of the building plan applications at this time. The following items need to be addressed: BUILDING PLAN COMMENTS: 1) Engineering could not verify that the building plan was in compliance with the stamped approved Development Plan Package (DP14-0030). Please submit a copy of the stamped approved Development Plan Package with the next building plan submittal. 2) Engineering will re-review the building plan on the next submittal to insure compliance with the approved and stamped Development Plan Package. Additional comments may be forthcoming. GENERAL COMMENTS: Please provide the building plan with a copy of the last approved Development Plan Package (DP14-0030). Further comments may be generated upon resubmittal of the building plan review. For questions or to schedule an appointment I can be reached at 837-4929. Jason Green, CFM Senior Engineer Associate Engineering Division Planning & Development Services |
| 04/11/2014 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: FedEx Ground Co-Location T14CM01923 Building Plan (1st Review) TRANSMITTAL DATE: April 11, 2014 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning has reviewed the building plans but cannot approve until a development package has been submitted and approved for the site changes 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 04/16/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET G-01: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE BUILDING CODE INFORMATION. 2. SHEET G-01; BUILDING CODE INFORMATION: REVISE THE DATE ON THE ICC/ANSI EDITION. 3. SHEET G-01; BUILDING CODE INFORMATION: THE OCCUPANCY CLASSIFICATION REFERENCES SECTION 308. REVISE. 4. SHEET G-01; BUILDING CODE INFORMATION: THE CONSTRUCTION CLASSIFICATION REFERENCES TABLE 602 AND SECTION 602.2. REVISE. 5. SHEET G-01; BUILDING CODE INFORMATION: THE MINIMUM NUMBER OF EXITS REFERENCES TABLE 1021.1 AND TABLE 1015.1. REVISE. 6. SHEET G-01; BUILDING CODE INFORMATION: THE EXIT DISCHARGE REFERENCES SECTION 1021.1 AND 1015.1. REVISE. 7. SHEET G-01; BUILDING CODE INFORMATION: THE EXIT TRAVEL DISTANCE REFERENCES TABLE 1016.1. REVISE. 8. SHEET G-01; BUILDING CODE INFORMATION: THE EGRESS WIDTH REFERENCES SECTION 1005.1. REVISE (STAIRWAYS USE 0.3 FACTOR). 9. SHEET G-01; BUILDING CODE INFORMATION: THE MINIMUM NUMBER OF EXITS FOR THE S-1 PORTION OF THE BUILDING INDICATES 3 EXITS ARE REQUIRED. THE IBC SECTION 1021.2.4 INDICATES 3 EXITS ARE REQUIRED FOR OCCUPANT LOADS OF 501 TO 1000. VERIFY. 10. SECTION G-01; BUILDING CODE INFORMATION: THE STAIRWAY SERVING 50 OCCUPANTS OR LESS REFERENCES SECTION 1009. REVISE. 11. SHEET G-01; BUILDING CODE INFORMATION: IS THE CONSTRUCTION TYPE (LISTED AS VB) CORRECT? IF SO, WHERE DID THE MAXIMUM ALLOWABLE BUILDING AREAS FOR B AND S-1 (TABLE 503) COME FROM? PROVIDE CALCULATIONS ON THE DRAWINGS FOR THIS. 12. SHEET ADA-1: THIS PROJECT'S ACCESSIBILITY REQUIREMENTS WILL FOLLOW THE 2012 IBC AND THE 2009 ICC/ANSI A117.1. REVISE THIS SHEET AS REQUIRED. 13. SHEETS ADA-1, ADA-2, ADA-3, AND ADA-4: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE VERBIAGE. SHEETS CAN BE REDUCED IN NUMBER BY INCLUDING ONLY THOSE REQUIREMENTS SPECIFIC TO THIS PROJECT. 14. SHEETS A001a AND A001b: A BOXED NOTE REFERENCES TABLE 1016.1 FOR EXIT TRAVEL DISTANCE. REVISE. 15. SHEET A101b; FLOOR PLAN: SECTION A/A201a IS CUT THROUGH THE ENTIRE BUILDING ON THE PLAN, BUT THE SECTION ON A201a ONLY EXTENDS TO GRID 7. VERIFY. 16. SHEETS A101a AND A101b (FLOOR PLAN); DETAIL 05/A302: THE IBC SECTION 1007.7 (EXTERIOR AREA FOR ASSISTED RESCUE) INCLUDES A SECTION 1007.7.4 CONCERNING THE SEPARATION OF THE EXTERIOR WALL FROM THE AREA OF ASSISTED RESCUE. VERIFY THE REQUIREMENTS OF THIS SECTION HAVE BEEN MET. 17. SHEET A200c; EXTERIOR ELEVATIONS: PROVIDE SECTION CUTS ON THE ELEVATIONS. 18. SHEET A302; STAIR PLAN 5: CLEAR UP THE DIMENSIONS. 19. SHEET A302; STAIR PLAN 5: CLEAR UP THE VERBIAGE AT THE LOW PIPE BOLLARD. 20. SHEET A302; STAIR PLAN 5: A NOTE REFERENCES 1/A101 FOR PIPE BOLLARD LOCATIONS. REVISE THE REFERENCE. 21. SHEET A400; KEYED NOTES: NOTES 22 AND 39 WERE NOT LOCATED ON THE PLAN. VERIFY. 22. SHEET A402a; ELEVATION 21: PROVIDE A DETAIL ON THE DRAWINGS FOR THE SUPPORT OF THE 20 GALLON HOT WATER HEATER ABOVE THE CEILING. 23. SHEET A402a; ENLARGED RESTROOM PLAN: ON THE RIGHT SIDE OF THE PLAN, AN ELEVATION 03/A402a IS INDICATED AT THE HIGH/LOW DRINKING FOUNTAIN. REVISE THE ELEVATION REFERENCE. 24. SHEET A402b; ENLARGED RESTROOM PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE INSIDE ELEVATION INDICATORS. 25. SHEET A402b; ENLARGED RESTROOM PLAN (LEGEND): REFERENCE IS MADE TO 2/A400 FOR WALL TYPES. REVISE THE REFERENCE. 26. SHEET A402b; ENLARGED RESTROOM PLAN: THE SECTION CUT REFERENCES 11/A402b. REVISE THE REFERENCE. 27. SHEET A502; SECTION 17: THE RIGHT SIDE OF THE COUNTER INDICATES A DIMENSION 3'-2" (ADA). THE ICC/ANSI REQUIRES 2'-10". VERIFY. 28. GENERAL: PER THE IBC SECTION 1109.5, IF THREE DRINKING FOUNTAINS ARE REQUIRED AND FOUR ARE PROVIDED, (PER SHEET G-01), TWO SHOULD ACCOMODATE PEOPLE IN WHEEL CHAIRS, AND TWO SHOULD ACCOMODATE STANDING PEOPLE. FROM SHEETS 402a AND 402b, IT APPEARS THERE ARE 3 FOR WHEEL CHAIRS AND 1 FOR STANDING. VERIFY. 29. GENERAL: VERIFY THE 3/32" MINIMUM LETTER HEIGHT IS MET ON ALL SHEETS. 30. GENERAL STRUCTURAL: VERIFY THERE ARE NO STRUCTURAL DRAWINGS/SECTIONS/DETAILS REQUIRED IN ADDITION TO THE PREVIOUSLY SUBMITTED FOUNDATION PLAN (T14CM01254) OR THE DEFERRED SUBMITTAL OF THE PRE-ENGINEERED METAL BUILDING. 31. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 04/25/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the design basis for the natural gas piping. The boxed note on sheet PL101 calls for 2 PSIG service with a pressure reducing valve at the location of each appliance but the pipe sizes suggest that low pressure gas was supplied to the entire building. Reference: Section402.1, IFGC 2012. 2. Provide water supply isometrics. Reference: Section 107.2.1, IBC 2012. 3. The two electric water heaters are mounted on platforms. Provide a design for the platforms along with structural calculations to show that the water heaters are safely supported. Reference: Section 301.2, IPC 2012. 4. Provide the specifications and listing information for the proposed gas-fired water heater, GFWH1 shown o sheet PL102. Reference: Sections 303.2 and 501.5, IPC 2012 and Section 107.2.1, IBC 2012. 5. Provide details for the installation of the three water heaters, including the excess pressure relief, expansion tank, vacuum relief or other anti-siphon device, safety pan, and valves. Reference: Sections 503, 504, 606.1, 607.2, and 607.3, IPC 2012. 6. If the specified water heaters are not supplied with integral heat traps or on recirculating hot water systems, provide heat traps on the supply and discharge piping and install 0.5" of insulation with a maximum conductivity of 0.27 BTU per inch/h F on the first 8 feet of supply and discharge piping. Reference: Sections C404.4 and C404.5, IECC 2012. 7. Symmons does not list a current temperature mixing valve with the catalog number of 5-210-ck. Provide listing information for an approved device conforming to ASSE 1070 to deliver tempered water to the lavatories and public hand-washing sinks in restrooms. Reference: Sections 416.5 and 607.1.2, IPC 2012. 8. Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson. 9. Provide calculations showing how the water supply piping has been sized. Reference: Sections 604.1 and 604.3, IPC 2012. 10. Verify that the pipe sizes called out for the flush valves will not result in water velocities greater than that recommended by the pipe manufacturer (e.g. limit the water velocity to less than 8 FPS for copper tubing). At a minimum design flow rate of 25 GPM for a siphonic, flush-valve water closet, a 1" Type L copper tube has a flow velocity of 9.7 FPS. Reference: Table 604.3, IPC 2012. 11. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves. Reference: Section 604.9, IPC 2012. 12. The developed length of the hot water supply piping from EWH1to the furthest wash fountain it serves appears to be greater than fifty feet; provide a method for maintaining the temperature of the hot water supply system. Reference: Section 607.2, IPC 2012. |
| 04/25/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the font size used on the drawings to a minimum height of 3/32-inch. Reference: Section 107.2.1, IBC 2012. 2. The Mechanical Compliance Certificate on sheet M503 is not legible; revise the font size or submit the Mechanical Compliance Certificate separately on 8.5x11" sheets. Complete the Mechanical Compliance Certificate by checking the appropriate line items in Section 4, the Requirements Checklist. Reference: Section 107.2.1, IBC 2012. 3. Provide energy code compliance calculations for the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2012. 4. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012. 5. Provide notes on the drawings indicating provisions for commissioning the mechanical building systems per Section C408.2, IECC 2012. 6. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms during business hours will be exhausted regardless of the number of people in the restroom. Reference: Section 403.2.1 (4), IMC 2012. 7. Revise the mechanical design as required to avoid using the corridor as a return air duct (ACU-4). Reference: Section 601.2, IMC 2012. |
| 04/25/2014 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Tucson Water limits 2" water meters to maximum demand of 120-GPM. Verify that the calculated demand for the new plumbing fixtures (predominately a flush valve system) plus demand from the 52 evaporative coolers will not cause the total demand to exceed the allowable limit. Reference: Section 107.2.1, IBC 2012. |
| 05/05/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | 1) City of Tucson Oudoor Lighting Code section 104.2.1 requires Lumen calculation on plans. There shall be documentation on the plans to demonstrate compliance with the lumen cap per Table 401.1, and which includes the following information: a) Each exterior luminaire type with the lumens for that type, the quantity of each type and whether the luminaire is full cut-off or unshielded. b)The total of full cut-off and unshielded lumens for the parcel. c) A statement of the lighting area, the size of the permitted parcel, and the maximum allowed full cut-off and unshielded lumens. 2) City of Tucson requires a minimum font size of 3/32". Rework electrical detail sheets to meet this requirement (E401, E402, E403, E404 sheets) |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/24/2014 | CPIERCE1 | REJECT SHELF | Completed |