Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T14CM01892
Parcel: 12101103E

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM01892
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/23/2014 MICHAEL ST. PAUL ZONING REVIEW Approved
04/23/2014 MARTIN BROWN FIRE REVIEW Denied Fire Review Comments:
1. Please indicate on which page the Exit signs are located and the required emergency egress lighting.
2.Need additional information on the installation and use of the 1,000 Gallon Aboveground Tank of Cyrogenic Liquid Nitrogen:
A. Please indicate compliance with the following 2012 IFC code sections:
Piping:5003.2.2, 5003.2.2.1, 5003.2.2.2
Foundation and Supports: 5503.1.3, 5503.1.3.1
Separation Distances: Table 5504.3.1.1
Use and Handling in Section 5505

I understand that the plans indicated that another contractor will install the tank, but the location of the tank and all related piping that is going to be installed in the building needs to be shown on this plan.

Thanks , Ken Brouillette
04/28/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/28/2014 ROBERT SHERRY WATER REVIEW Approved
04/30/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide descriptions of the tenant-provided equipment being installed. Include listing information, safety data sheets (as applicable), sizes and capacities, installed weights (for items to be installed on the roof), installation instructions, and material requirements for inter-connecting piping. Reference: Section 107.2.1, IBC 2012.
2. Verify the presence of liquid nitrogen piping inside of the building (downstream of a properly-sized vaporizer, only gaseous nitrogen should be involved). Reference: Section 107.2.1, IBC 2012.
3. Verify that any contaminant sources within the lab (e.g. fumes, vapors, gases, etc.) that could constitute a health hazard are collected and removed from the lab. Reference: Section 401.6, IMC 2012.
4. Determine the minimum required ventilation and make-up air quantities for the lab a show how the air will be introduced into the lab. Reference: Section 403.2, IMC 2012.
05/08/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
05/12/2014 AROMERO4 APPROVAL SHELF Completed
05/12/2014 AROMERO4 OUT TO CUSTOMER Completed
05/12/2014 CPIERCE1 REJECT SHELF Completed