Permit Number: T14CM01878
Parcel: 14042038C

Address:
6550 S TUCSON BL

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T14CM01878
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/30/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET C1; SITE PLAN: THREE OF THE NEW STRUCTURES INDICATE THE ROOF EXTENDING TO THE PROPERTY LINE. PER THE IBC SECTION 705.2, A PROJECTION REQUIRING A FIRE SEPARATION DISTANCE OF 2' TO 5' MUST BE AT LEAST 24" FROM THE LINE OF FIRE SEPARATION. INDICATE ON THE PLAN AND ON DETAIL ONE THAT THE ROOF PROJECTION IS A MINIMUM OF 24" FROM THE PROPERTY LINE.
2. SHEET C1; SITE PLAN: THREE OF THE NEW STRUCTURES INDICATE THE ROOF EXTENDING TO THE PROPERTY LINE. PER THE IBC SECTION 406.3.2(2), A STRUCTURE WITHOUT ANY FIRE RESISTIVE RATING CAN BE ERECTED PROVIDED THE VERTICAL STRUCTURAL SUPPORTS HAVE A FIRE SEPARATION DISTANCE FROM THE LINE OF FIRE SEPARATION OF 5' OR MORE. INDICATE ON THE PLAN AND ON DETAIL 1 THAT THE VERTICAL SUPPORT COLUMN IS LOCATED A MINIMUM OF 5' FROM THE PROPERTY LINE.
3. SHEET C1; SITE PLAN: IN THE SOUTHEAST PORTION OF THE SITE (JUST SOUTH OF THE ENTRY), THERE IS A PARKING STRUCTURE (36' X 126') THAT DOES NOT INDICATE IF IT IS A NEW OR EXISTING STRUCTURE (NOTE 4 OR NOTE 42). VERIFY.
4. SHEET C1; SITE PLAN: IN THE NORTHEAST PORTION OF THE SITE (JUST NORTH OF THE ENTRY), A PARKING STRUCTURE (18' X 180') IS MARKED AS EXISTING COVERED PARKING (NOTE 4), AND AS NEW COVERED PARKING (NOTE 42). CLARIFY.
5. SHEET C1; SITE PLAN: IN THE SOUTHWEST PORTION OF THE SITE, THERE IS A 18' X 198' PARKING STRUCTURE AND A 18' X 27' PARKING STRUCTURE MARKED AS NEW PARTIAL COVERED PARKING (NOTE 43). VERIFY IF THESE ARE NEW OR EXISTING STRUCTURES.
6. SHEET 2: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE GENERAL STRUCTURAL NOTES AND DETAIL VERBIAGE.
7. SHEET 2; GENERAL STRUCTURAL NOTES (FOUNDATIONS): REFERENCE IS MADE IN THE FIRST NOTE TO IBC SECTIONS 1804, 1804.3.1, AND 1805.7.2.2 FOR CAISSON FOOTING DESIGN. REVISE THESE NOTES TO THE 2012 IBC.
8. SHEET 2; GENERAL STRUCTURAL NOTES (FOUNDATIONS): REFERENCE IS MADE IN THE SECOND NOTE TO THE IBC SECTION 1804. REVISE THE NOTE TO THE 2012 IBC.
9. STRUCTURAL CALCULATIONS; SHEET NUMBER 7.0: THE TWO NOTES INDICATE TO VERIFY THE SOIL CLASS WITH THE SOILS REPORT. NO REPORT IS PROVIDED. EXPLAIN.
10. GENERAL: A SPECIAL INSPECTION FORM IS REQUIRED FOR THE FIELD WELDING. PROVIDE.
11. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/09/2014 AROMERO4 APPROVAL SHELF Completed
05/09/2014 AROMERO4 OUT TO CUSTOMER Completed
05/09/2014 CPIERCE1 REJECT SHELF Completed