Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T14CM01874
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/14/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide structural drawings showing all required structural details shown in the calculations. 2. Provide structural foundation details and calculations. 3. Revise all architectural drawings showing the ramp (This includes all architectural plans and details) and details to match those as designed in the structural calculations. Include these sheet changes in the revision submittal. 4. Show how the ramp landing is connected to the existing stair landing. 5. Provide a set of the approved permit drawings for referral with the Deferred submittal package. END OF REVIEW |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/02/2014 | SHANAE POWELL | OUT TO CUSTOMER | Completed |