Review Date Reviewer's Name Type of Review Description Status Comments
10/07/2014 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T14CM01869
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL COMMENTS:

1. Limit all code references to those recognized by the City of Tucson. Adopted 2012 codes are listed at the Planning & Development Services web site. Update the code reference used at note #5 sheet A.4.

FOUNDATION PLANS:

1. Locate and detail all footings (R301.1). Show a footing at the center Patio Cover post on sheet #A.3.

STRUCTURAL PLANS:

1. Show a beam size with appropriate load carrying capacity at the Bonus Room, R301.1. The 4 x 8 beam requires replacement or a support post/footer that reduces the clear span.

SECTIONS - DETAILS:

1. Show the Wall Detail with minimum of one #4 rebar in the proposed continuous footing, R403.1 amendment. Update the wall footing detail on sheet A.3 and remove the "each way" notation.

PLUMBING PLANS:

1. Show a plumbing plan for the rooms built without permit, R301.1.
2. Show gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). Provide a gas line isometric or table for showing the BTU demand and length of line to each gas appliance.

MECHANICAL PLANS:

1. Provide heating facilities in all habitable rooms, R303.9. Include the Bonus Room and Carport Enclosure.

ELECTRICAL PLANS:

1. Notate that smoke alarms are required within and outside each separate sleeping area, R314.3.
2. Show or notate the requirement for a carbon monoxide detector outside of bedroom doors, when the dwelling includes an attached garage or gas appliance, R315.
3. Show receptacle outlets at wall spaces 2' or more with no wall point (exclude door openings) more than 6' from a receptacle outlet, E3901.2. Include the Bonus Room and Carport Enclosure.
4. Show receptacle outlets at each kitchen counter space wider than 12" with no point along the wall line more than 24" from a receptacle outlet, E3901.4.1. Show receptacles within 2' of counter edges or corners and no more than 4' apart.
5. Protect all 15A & 20A outlets (except bathrooms and kitchen) including receptacles, lights and smoke detectors with combination type arc-fault circuit interrupters, E3902.12.

OUTDOOR LIGHTING CODE

1. Show the proposed fixture as full cut-off FCO style, or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits. Adjustable security light fixtures are unshielded, not FCO.

If you have any questions please contact: