Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T14CM01867
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/09/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 04/21/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET S-100; GENERAL NOTES (SECTION 1.5): THE SPECIAL INSPECTION NOTES REFERENCE THE 2006 IBC SECTION 109. REVISE THE SECTION REFERENCE AND THE CODE EDITION. 2. SHEET S-100 (SECTION 9); STRUCTURAL CALCULATIONS (PAGE 6): THE DETAIL IN THE CALCULATIONS INDICATES THE FOUNDATION REINFORCING TO BE #6 BARS AT 12" EACH WAY (TOP LAYER REINFORCING) AND #6 BARS AT 6" EACH WAY (BOTTOM LAYER REINFORCING), WHILE THE SECTION ON THE DRAWING INDICATES #6 AT 12" EACH WAY TOP AND BOTTOM. CLARIFY. 3. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 04/30/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | CLARIFY PURPOSE OF LUMINAIRE H1. IS THIS A WORK LIGHT? IF THIS IS MEANT TO ILLUMINATE ANTENNA AT NIGHT THEN OUTDOOR LIGHTING CODE REQUIREMENTS MUST BE MET. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/05/2014 | AROMERO4 | APPROVAL SHELF | Completed |
| 05/05/2014 | AROMERO4 | OUT TO CUSTOMER | Completed |
| 05/05/2014 | CPIERCE1 | REJECT SHELF | Completed |