Permit Number: T14CM01850
Parcel: 13502134L

Review Status: Active

Review Details: COMMERCIAL - TI

Permit Number - T14CM01850
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
04/02/2014 DAVID RIVERA ZONING REVIEW Approved
04/02/2014 JASON GREEN ENGINEERING REVIEW Approved
04/03/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
04/03/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide HVAC load calculations.
2. Provide a 4" dryer vent.
04/03/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
04/03/2014 ROBERT SHERRY WATER REVIEW Approved
04/03/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the water demand calculations and adjust the pipe sizes as required.
2. Provide mixing valves for the lavatories conforming to ASSE 1070.
3. Provide a shower valve complying with the requirements of Section 424, IPC 2012.
4. Show how the shower will comply with the requirements of Section 416, IPC 2012.
5. Provide specifications for the urinal.
6. Provide water hammer arrestors for the clothes washer.
04/03/2014 MARTIN BROWN FIRE REVIEW Approved
04/03/2014 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/18/2014 AROMERO4 WWM REVIEW Completed