Permit Number: T14CM01784
Parcel: 125050460

Address:
2221 E 4TH ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T14CM01784
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/31/2014 STEVE SHIELDS ZONING REVIEW Denied P&DS TRANSMITTAL


FROM: Steve Shields, Lead Planner

PROJECT:
T14CM01784
2221 E. 4th Street
Add bedroom, bath, enlarge living/family room and add two car garage.


TRANSMITTAL: April 3, 2014


COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).


This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A).

Based on a wall height of 9'-6" the required west perimeter yard setback is 6'-4", proposed west perimeter yard setback is 4'-0".

Based on a wall height of 12'-9" the required north perimeter yard setback is 8'-6", proposed west perimeter yard setback is 6'-0".
03/31/2014 SSHIELD1 NPPO REVIEW Passed
11/24/2014 AROMERO4 ENGINEERING REVIEW Needs Review
11/24/2014 AROMERO4 BUILDING-RESIDENTIAL REVIEW Needs Review