Permit Number: T14CM01744
Parcel: 10821018Y

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM01744
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/28/2014 MICHAEL ST. PAUL ZONING REVIEW Approved
03/28/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The City of Tucson did not adopt ASHRAE Standard 62.1 for ventilation calculations and the 2012 IMC only references the ASHRAE Standard for the purpose of calculating the system ventilation efficiency (Ev). Provide calculations to show that the ventilation system is sized in accordance with Section 403.3, IMC 2012.
03/28/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
03/28/2014 ROBERT SHERRY WATER REVIEW Approved
03/28/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved 1. Need to provide a "Point of Use" water dispenser.
03/28/2014 CPIERCE1 WWM REVIEW Passed
03/28/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide tempered water for the lavatories located in restrooms using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
03/28/2014 CPIERCE1 ENGINEERING REVIEW Needs Review
03/28/2014 MARTIN BROWN FIRE REVIEW Approved
03/28/2014 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed