Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T14CM01709
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/30/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. PREVIOUS COMMENT 1: THE WOMEN'S RESTROOM IS NOT AN ACCESSIBLE ROOM. SINCE IT IS AN EXISTING RESTROOM, IT DOES NOT REQUIRE A CHANGE IN ORDER TO MEET ACCESSIBILITY STANDARDS. REVISE NOTE IN RESTROOM, AND INDICATE HOW AN ACCESSIBLE RESTROOM CAN BE CREATED FOR BOTH SEXES. |
| 04/30/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Comment not resolved; provide material standards for the plumbing fixtures not produced by Kohler (e.g. stainless steel sinks).[Initial comment: Provide material standards for all plumbing fixtures being provided by others. Reference: Sections 303.4 and 402, IPC 2012.] 2. Verify that the vent for the floor sink rises vertically to at least 6" above the flood rim of the floor sink prior to running horizontally. Reference: Section 905.4, IPC 2012. [Initial comment: Show the floor sink located in the mechanical room has been vented in accordance with one of the methods shown in the IPC. Reference: Section 901.2.1, IPC 2012.] |
| 04/30/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved |