Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T14CM01709
Parcel: 121082780

Address:
1221 N WILMOT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM01709
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/30/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT 1: THE WOMEN'S RESTROOM IS NOT AN ACCESSIBLE ROOM. SINCE IT IS AN EXISTING RESTROOM, IT DOES NOT REQUIRE A CHANGE IN ORDER TO MEET ACCESSIBILITY STANDARDS. REVISE NOTE IN RESTROOM, AND INDICATE HOW AN ACCESSIBLE RESTROOM CAN BE CREATED FOR BOTH SEXES.
04/30/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not resolved; provide material standards for the plumbing fixtures not produced by Kohler (e.g. stainless steel sinks).[Initial comment: Provide material standards for all plumbing fixtures being provided by others. Reference: Sections 303.4 and 402, IPC 2012.]
2. Verify that the vent for the floor sink rises vertically to at least 6" above the flood rim of the floor sink prior to running horizontally. Reference: Section 905.4, IPC 2012. [Initial comment: Show the floor sink located in the mechanical room has been vented in accordance with one of the methods shown in the IPC. Reference: Section 901.2.1, IPC 2012.]
04/30/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved