Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM01709
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/07/2014 CPIERCE1 BUILDING-COMMERCIAL REVIEW Needs Review
04/16/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the specified U-factor for the new fixed windows to be a maximum of 0.50 (not a minimum of 0.56) and with a maximum Solar Heat Gain Coefficient (SHGC) of 0.25 for the windows per Table C402.3, IECC 2012. Reference: Sections C103.2 and C402.3, IECC 2012.
2. Show that the proposed replacement rooftop units meet the requirements of Sections C403.2.2, C403.2.3, C403.2, and C403.3 (e.g. provide the mechanical energy code compliance certification from COMcheck). Reference: Section C303.1, International Energy Conservation Code 2012.
3. Clarify the scope of work for this activity. Items #8 and #9 in the Mechanical General Notes refer to fan coil units being relocated but no such units are shown on the plans. Reference: Section 107.2.1, IBC 2012.
4. Clarify the detail call outs for 1/M2 and 2/M2 on the mechanical roof plan. Reference: Section 107.2.1, IBC 2012.
5. Coordinate the call outs for the supply air diffusers with the legend on sheet M1. Reference: Section 107.2.1, IBC 2012.
6. Show the size, routing, and termination of the condensate drain for AC-5. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson.
7. Show the balancing information for the new heat pumps. The three new heat pumps each serve multiple zones and it is impossible to calculate the required ventilation efficiency value (Ev) for each zone without the balancing data. Reference: Sections 403.3.2.3.1 and 403.7, IMC 2012.
8. A clothes washer is shown in the mechanical room. If a dryer is to be installed, show the size, route, and termination of the dryer exhaust duct. Reference: Sections 504.1, 504.2, 504.4 and, 504.6, IMC 2012.
04/16/2014 ROBERT SHERRY WATER REVIEW Approved
04/22/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide structural calculations for the mounting shelf for the water heater to show that the water heater will be safely supported from the building structure (i.e. will the wall withstand the load imposed by the water heater). Reference: Section 301.2, IPC 2012.
2. Provide material standards for all plumbing fixtures being provided by others. Reference: Sections 303.4 and 402, IPC 2012.
3. The trap and fixture drain for a standpipe serving an automatic clothes washer shall be no smaller than 2 inches. Reference: Section 406.2, IPC 2012.
4. The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3-inches in diameter. Reference: Section 406.2, IPC 2012.
5. Show how the temperature of the hot water supply to the public lavatories is to be controlled. Reference: Sections 416.5, 607.1, and 607.1.1, IPC 2012 and Section C404.3, IECC 2012.
6. Provide an automatic faucet for the new lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson.
7. Provide cleanouts for all horizontal fixture branch drains; the cleanouts shall be sized per Section 708.7, IPC 2012 and shall open to allow cleaning in the direction of flow. Reference: Sections 708.3.1 and 708.5, IPC 2012.
8. Show the floor sink located in the mechanical room has been vented in accordance with one of the methods shown in the IPC. Reference: Section 901.2.1, IPC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/30/2014 FERNE RODRIGUEZ REJECT SHELF Completed