Permit Number: T14CM01679
Parcel: 12809006B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM01679
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/26/2014 MICHAEL ST. PAUL ZONING REVIEW Approved
03/26/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/26/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
03/26/2014 ROBERT SHERRY WATER REVIEW Denied Provide the size of the existing water meter and the total demand it serves.
03/26/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change 1. Provide hi/low water dispenser as per code.
2. If additive alternate for suspended water heater is accepted provide structural details and calculations.
03/26/2014 JASON GREEN ENGINEERING REVIEW Approved
03/26/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide a hi-low drinking fountain.
Correct keynote 1, P1.0 in the existing women's restroom.
03/26/2014 MARTIN BROWN FIRE REVIEW Denied Please provide quantities of gases (oxygen and any others ) contained in room 122, oxygen storage room. Refer to chapter 50 of the 2012 International Fire Code for guidelines.
Be advised annual sprinkler inspections required by the code will need to be current prior to C of O being isspued.
03/26/2014 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/09/2014 SPOWELL1 WWM REVIEW Needs Review