Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T14CM01565
Parcel: 134161990

Address:
7433 E 22ND ST

Review Status: Active

Review Details: COMMERCIAL - TI

Permit Number - T14CM01565
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
03/20/2014 DAVID RIVERA ZONING REVIEW Approved
03/20/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/20/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
03/20/2014 ROBERT SHERRY WATER REVIEW Approved
03/20/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
03/20/2014 RSHERRY1 WWM REVIEW Passed No wastewater plumbing.
03/20/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/20/2014 JASON GREEN ENGINEERING REVIEW Approved
03/20/2014 MARTIN BROWN FIRE REVIEW Approved
03/20/2014 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed