Permit Number: T14CM01547
Parcel: 12302248B

Address:
2520 E LESTER ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T14CM01547
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2014 RAFAEL CANCINO BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS

Date: March 14, 2014
Activity: T14CM01547
Address: 2520 E. Lester St.
Applicant: Mr. Dave Shambach


Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide revised plans and calculations, highlighting any changes or with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2012 IRC with amendments on 1/1/2012. Show the code references on the plans.

GENERAL NOTES:

" Limit all code references to those recognized by the City of Tucson. Adopted 2012 codes are listed at the Planning & Development Services web site. Show the code references used for the design.
" Please make spelling corrections to sheet A1.1.


FLOOR PLAN/FRAMING PLAN:

1. Section 1 of new bathroom calls for sheet A4. There is no sheet A4 in plans.

SHEET A3:

1. Section 2 detail calls for 2X8 ledger on 2X10 rafter, Please changer ledger size to 2X10. Also, specify size of anchor bolts.

PLUMBING PLAN:

1. Show gas piping calculations.
2. Change location of water lines in existing bathroom to lavatory location.
3. Correct water fixture units to reflect 2012 units.

MECHANICAL PLAN:

1. Provide Manual J, S and D calculations.

ELECTRICAL PLAN:

1. Install GFCI outlet by lavatory area.

If you have any questions please contact:

Rafael Cancino
(520) 909-4891
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/16/2014 SHANAE POWELL OUT TO CUSTOMER Completed
04/16/2014 CPIERCE1 REJECT SHELF Completed