Permit Number: T14CM01544
Parcel: 110120950

Address:
2424 N WYATT DR

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM01544
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/25/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET G-001; INDEX OF DRAWINGS: SHEETS S-200, S-300, S-301, S-302, A-001, A-202, A-302, A-500, A-506, A-800, AND A-801 ARE LISTED IN THE INDEX, BUT ARE NOT INCLUDED IN THE SET. REVISE.
2. SHEET S-01; FOUNDATION NOTES: NOTE 1 INDICATES A SOIL REPORT WAS USED FOR THE FOUNDATION DESIGN. PROVIDE THAT REPORT (ONE COPY) FOR REVIEW.
3. SHEET S-110; FOUNDATION PLAN: AT GRIDS O AND 6, A SECTION 5/S-503 IS CUT. REMOVE THAT SECTION CUT, OR REVISE.
4. SHEET S-110; FOUNDATION PLAN: AT GRIDS O AND 1, A DETAIL 1/S-502 IS INDICATED. REVISE THAT TO A SECTION CUT.
5. SHEET S-120; KEYNOTES: IN KEYNOTE 2, SPECIFICALLY REFERENCE DETAIL 1A/S-500.
6. SHEET S-500; DETAIL 1Q: ARE THESE DETAILS USED ON THIS PROJECT? VERIFY.
7. SHEET S-503; SECTIONS 3 AND 4: ARE THESE SECTIONS IDENTICAL? VERIFY.
8. SHEET D-110; DEMOLITION KEYED NOTES: PROVIDE A NOTE ON THE DRAWING THAT NOT ALL KEYED NOTES ARE ON EACH SHEET.
9. SHEET D-120; DEMOLITION KEYED NOTES: PROVIDE A NOTE ON THE DRAWING THAT NOT ALL KEYED NOTES ARE ON EACH SHEET.
10. SHEET A-110; FLOOR PLAN: SEVERAL DETAILS REFERENCE SHEET A-500. THERE IS NO SHEET A-500 IN THIS SET. CLARIFY.
11. SHEET A-110 (FLOOR PLAN); SHEET A-201 (ELEVATION F1): THE PLAN ON A-110 INDICATES THE ELEVATION ON THE LEFT SIDE OF THE BUILDING PLAN, WHILE THE REFERENCE PLAN ON THE ELEVATION INDICATES THE RIGHT SIDE OF THE BUILDING PLAN. CLARIFY.
12. SHEET A-110; FLOOR PLAN: AN ELEVATION REFERENCES SHEET A-202. THERE IS NO SHEET A-202 IN THIS SET. CLARIFY.
13. SHEET A-120; FLOOR PLAN: SEVERAL DETAILS REFERENCE SHEET A-500. THERE IS NO SHEET A-500 IN THIS SET. CLARIFY.
14. SHEET A-120; FLOOR PLAN: SEVERAL DETAILS REFERENCE SHEET A-500. THERE IS NO SHEET A-500 IN THIS SET. CLARIFY.
15. SHEET A-120; FLOOR PLAN: AN ELEVATION REFERENCES SHEET S-202. THERE IS NO SHEET A-202 IN THIS SET. CLARIFY.
16. SHEET A-120 (FLOOR PLAN); SHEET A-201 (ELEVATION F1): THE PLAN ON A-120 INDICATES THE ELEVATION ON THE LEFT SIDE OF THE BUILDING PLAN, WHILE THE REFERENCE PLAN ON THE ELEVATION INDICATES THE RIGHT SIDE OF THE BUILDING PLAN. CLARIFY.
17. SHEET A-150: THE SHEET FOLLOWING A-130 IS NOT NUMBERED. PROVIDE.
18. SHEET A-300; SECTION B1: WHAT IS THE 29'-4" DIMENSION IN REFERENCE TO? VERIFY.
19. SHEET A-301; SECTION B1: THE SECTION REFERENCES DETAILS ON SHEETS A-500 AND A-506. THERE ARE NO SHEETS A-500 AND A-506 IN THIS SET. CLARIFY.
20. GENERAL: THIS IS THE FIRST CITY OF TUCSON REVIEW OF THIS PROJECT. REMOVE THE REVISION CLOUDS AND REVISION NOTE/BID NOTE IN THE TITLE BLOCK FOR ALL PERTINENT SHEETS.
21. GENERAL: THE VALUATION FOR THIS PROJECT HAS BEEN ESTABLISHED ONLY FOR THE ADDITION OF THE TWO NEW SHADE STRUCTURES. PROVIDE A WRITTEN CONSTRUCTION COST ESTIMATE (LABOR AND MATERIALS) FOR THE ENTIRE RENOVATION. INDICATE IF THE NEW SHADE STRUCTURES ARE INCLUDED IN THIS ESTIMATE.
22. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
04/01/2014 ROBERT SHERRY WATER REVIEW Approved
04/01/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/01/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/09/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Reqs Change T14CM01544

1. Remove clouding from plans submitted for the first review.

2. Provide 2012 IECC (interior) lighting calculation: use ComCheck report, or Table C405.5.2(1) building area or (2) space-by-space for budget determination.
a. Provide interior lighting control in compliance with C405.2.1.1.
b. Provide interior lighting reduction control in compliance with C405.2.1.2.

Ken Van Karsen
Elect Plan Review
PDSD, City of Tucson
520-837-4912
Kenneth.VanKarsen@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
04/23/2014 CPIERCE1 REJECT SHELF Completed