Review Date Reviewer's Name Type of Review Description Status Comments
04/03/2014 STEVE SHIELDS ZONING REVIEW Approved
04/08/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change SHEET CVR
1. How about providing a Tucson, Arizona Vicinity Map as opposed to the Columbus, MS one on this sheet.
2. The building occupancy is being changed from the current CofO occupancy load of 107 to 99. Please provide a complete seating floor plan showing occupancy loads and seating including accessible seating required.
3. Please correct the accessible code to the 2009 ICC A117.1 not the 2003 as listed.
SHEETS AS1 AND AS2
4. Why are these sheets included if all the necessary accessible details are already shown on sheet A1.1?
SHEET A0.0
5. Please delete the ADA reference at note 3 and reference the 2009 ICC A117.1.
SHEET A1.1
6. At detail 14:
a. Delete the the door mounted signage. Reference the wall mounted signage to the 2009 ICCA117.1, Section 702.
b. If the toilet room doors have both a closer and a latch, change the 11" jamb clearance to 12". Please confirm and note the existing conditions on the drawings.
END OF REVIEW
04/09/2014 LOREN MAKUS ENGINEERING REVIEW Approved
04/23/2014 AROMERO4 ELECTRICAL-COMMERCIAL REVIEW Needs Review