Review Date Reviewer's Name Type of Review Description Status Comments
03/19/2014 JASON GREEN ENGINEERING REVIEW Approved March 19, 2014
FLOODPLAIN USE PERMIT NO.: T14OT00315
ADDRESS: 3800 E River Rd Tucson, Arizona 85718
PROPERTY OWNER: JCC
3800 E River Rd Tucson, Arizona 85718

The applicant is authorized to use a portion of the FEMA Special Flood Hazard Area Zone A floodplain per the Flood Insurance Rate Maps 04019C1693L, specifically described as:

A portion of Parcel 111-01-035C

For the purpose of constructing a second story addition to an existing conforming structure.

The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard, and Watercourse Amenities, Safety and Habitat regulations, and is particularly bound by the conditions stated below. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Responsibility for renewal of this permit, if necessary, is with the applicant. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Unified Development Code, or any other Federal, State, County, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under City of Tucson Floodplain and Erosion Hazard Regulations and Watercourse Amenities, Safety, and Habitat regulations require the issuance of an additional Floodplain Use Permit.

Per the approved Development Plan for the Tucson Jewish Community Center, Elevation Certificate, and Master Drainage Report prepared by Cella Barr Associates "Hydrologic Analysis for Site Grading of Tucson Jewish Community Center CBA No.04049-05-30 the existing building is in conformance with the NFIP and has a set Finish Floor Elevation. The building finals and survey stamped ELCERT confirms that the building was constructed per the site plan making it a conforming structure.

All proposed work is to be interior and for the 2nd story of the building and no work shall be completed outside of the building without submitting new plans and permits to verify conformance with Chapter 26 of the Tucson Code.

Renewal of this permit will require a new application, review and approval of that application by the City of Tucson, Planning & Development Services Department, Engineering Division. This permit may be renewed for up to one year, in the absence of Registered Plant authorization, at the sole discretion of the City Engineer or designated representatives.

This Floodplain Use Permit will be automatically revoked and becomes invalid if conditions are not complied with, as set forth in this permit.


APPLICANT NAME: MetroTED
ADDRESS: 88 W Cushing St Tucson, Arizona 85701
PHONE: 520-990-6866
OWNER: Jewish Federation of Southern AZ
ADDRESS: 3822 E River Road Tucson, Arizona 85718
PHONE: 520-299-3000

(EXPIRATION DATE) Month: 03 Day: 19 Year: 2015

SIGNATURE OF APPLICANT DATE

The applicant is authorized by the City Engineer to receive a floodplain use permit subject to the above referenced conditions and restrictions.
03/20/2014 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Reqs Change 1) PP A0.3 You have cited IBC section 507.6 for an unlimited area building. 507.6 does not apply to 2 story buildings. Provide corrected calculations, this building does not appear to meet the area limitations of a type IIB structure.

2) Provide complete information for the building envelope showing compliance with 2012 IECC sections C101.4.3 and C401 and C402

3) Remove "not for construction" notations on structural pages,

4) Justify re-use of W24x76 beam noted as "Over-stressed in Bending" pp 23 of structural calculations. Reconcile span length of this beam with pp 19 of calculations (35' vs 33')
03/20/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Completed
03/21/2014 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Passed
03/21/2014 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Passed
03/21/2014 MARTIN BROWN FIRE REVIEW Denied Can not review plans that are stamped "NOT FOR CONSTRUCTION"
03/21/2014 LHANLY1 WATER REVIEW Passed
03/25/2014 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Jewish Community Campus Building Expanison
T14CM01531
Building Plan (1st Review)

TRANSMITTAL DATE: March 25, 2014

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning has reviewed the building plans but cannot approve until a development package has been approved for the site changes

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956