Permit Number: T14CM01445
Parcel: 117067140

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM01445
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/13/2014 STEVE SHIELDS ZONING REVIEW Approved
03/13/2014 LOREN MAKUS ENGINEERING REVIEW Approved
03/13/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEETS A.002 AND A.003: REMOVE THE 'FOR COMMENT' NOTE IN THE TITLE BLOCK.
2. SHEET A.003; ROOM FIXTURE CALCULATIONS: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE NOTES.
3. SHEET A.004: PROVIDE A NOTE OR REFERENCE TO THE REQUIREMENT OF THE IBC SECTION 1210.2.2 FOR THE WALL FINISH IN THE RESTROOMS (SHEET A.005 FINISH SCHEDULE).
4. SHEET A.301; ELEVATION 3: A SECTION CUT 10/A.601 ON THE WALL IS NOT CORRECT. REVISE.
5. SHEET A.701; DOOR TYPES: C AND E ARE MISSING VERBIAGE. PROVIDE.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/13/2014 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
03/14/2014 MARTIN BROWN FIRE REVIEW Approved
03/17/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Corridors shall not be used as return ducts. Reference: section 601.2, IMC 2012.
2. Clarify the sequence of operation for the restroom exhaust fans. The fans shall operate whenever air is being supplied to the restroom. Reference: Section 403.2.1 (4), IMC 2012.
3. Provide identification of the dryer duct length per Section 504.6.5, IMC 2012.
03/17/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
03/17/2014 ROBERT SHERRY WATER REVIEW Approved
03/17/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide water hammer arrestors for the Clothes washer outlets. Reference: Section 604.9, IPC 2012.
2. Clarify the construction of the indirect waste receptor for the clothes washer. Reference: 802.4, IPC 2012.
03/24/2014 AROMERO4 WWM REVIEW Passed