Permit Number: T14CM01274
Parcel: 117061960

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T14CM01274
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/05/2014 MICHAEL ST. PAUL ZONING REVIEW Approved
03/05/2014 JASON GREEN ENGINEERING REVIEW Approved
03/05/2014 MARTIN BROWN FIRE REVIEW Approved
03/06/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide heating and cooling load calculations.
2. Provide ventilation calculations.
3. Show that the HVAC system meets the requirements of the 2012 IECC.
4. Revise the sequence of operation for the restroom exhaust fan so that all air introduced into the restroom is exhausted.
5. Show the size, route, and termination point for the A/C condensate drain.
03/06/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
03/06/2014 ROBERT SHERRY WATER REVIEW Needs Review
03/06/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change 1. Provide large scale detail of toilets, show all accessible requirements.
2. Provide two toilet rooms
3. Provide retaining wall section and structural calculations
4. Provide structural calculations for new roof top mounted HVAC equipment.
END OF REVIEW
03/06/2014 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/16/2014 CPIERCE1 WWM REVIEW Passed
04/16/2014 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review