Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM01274
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/05/2014 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 03/05/2014 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 03/05/2014 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/06/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide heating and cooling load calculations. 2. Provide ventilation calculations. 3. Show that the HVAC system meets the requirements of the 2012 IECC. 4. Revise the sequence of operation for the restroom exhaust fan so that all air introduced into the restroom is exhausted. 5. Show the size, route, and termination point for the A/C condensate drain. |
| 03/06/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 03/06/2014 | ROBERT SHERRY | WATER | REVIEW | Needs Review | |
| 03/06/2014 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide large scale detail of toilets, show all accessible requirements. 2. Provide two toilet rooms 3. Provide retaining wall section and structural calculations 4. Provide structural calculations for new roof top mounted HVAC equipment. END OF REVIEW |
| 03/06/2014 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 04/16/2014 | CPIERCE1 | WWM | REVIEW | Passed | |
| 04/16/2014 | CPIERCE1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |