Review Date Reviewer's Name Type of Review Description Status Comments
03/20/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change GENERAL
1. Provide completed first portion of the two part certification for special inspectors for review and approval.
2. Provide structural calculations for all roof top mounted HVAC equipment.
SHEET A1.1
3. Show seating layout and include seating for accessibility as per 2012 IBC, Section 1108.2.9.1 and 2009 ICC A117.1, Section 902.
SHEET A1.2
4. Reference comment number 1.
SHEET A1.3
5. Turn off the first floor fixture layer.
6. Show wall finish compliance as required by the 2012 IBC, Section 1012.2.
7. Include exposed lavatory piping insulation.
8. Provide toilet room signage as per the 2009 ICC A117.1, Section 703
SHEET A8.0
9. At detail 2, show compliance with 2012 IBC, Section 1108.2.9.1; 5% accessibility seating.
10. At detail 4, change the accessible handrail as per requiremnts of the 2009 ICC A117.1, Section 505.7.
SHEET S000
11. The City of Tucson lettering standard is 3/32" minimum, actual size, (Not font designation size) for both upper and lower case lettering. Revise all structural drawings to this minimum standard and resubmit.
12. All structural details and plans have line weight that is so light that it cannot be reproduced nor scanned. Please revise all structural details and plans with a heavier line weight and resubmit.
END OF REVIEW