Permit Number: T14CM01172
Parcel: 13817038A

Address:
480 E ELVADO RD

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T14CM01172
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET S-11 (GENERAL STRUCTURAL NOTES-CONCRETE); STRUCTURAL CALCULATIONS (PAGE 1 OF CONTROL BUILDING): THE CALCULATIONS LIST STRUCTURAL SLABS, BEAMS, WALLS, AND COLUMNS AS REQUIRING 4000 PSI CONCRETE, WHILE THE GENERAL NOTES ON SHEET S-11 DO NOT INCLUDE THIS REQUIREMENT. CLARIFY.
2. SHEET S-11 (GENERAL STRUCTURAL NOTES-FOUNDATIONS); STRUCTURAL CALCULATIONS (PAGE 1 OF CONTROL BUILDING): BOTH THE CALCULATIONS AND SHEET S-11 INDICATE THERE IS NO SOILS REPORT AVAILABLE. SHEET S-1 INDICATES THERE IS A GEOTECHNICAL REPORT. CLARIFY.
3. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
08/22/2014 MICHAEL ST. PAUL ZONING REVIEW Reqs Change Approval of DP14-0033 is required. The building plans must match the development package site when approved.
08/26/2014 JASON GREEN ENGINEERING REVIEW Reqs Change Building plan will be stamped approved for ENG purposes upon approval of DP14-0033.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/29/2014 SHANAE POWELL OUT TO CUSTOMER Completed
08/29/2014 CPIERCE1 REJECT SHELF Completed