Permit Number: T14CM01172
Parcel: 13817038A

Address:
480 E ELVADO RD

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T14CM01172
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/25/2014 MARTIN BROWN FIRE REVIEW Approved
04/29/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A-2; BUILDING CODE CHART: UNDER 'SEPARATION RATINGS', COMPLETE THE LAST DISTANCE ('DISTANCE MORE THAN __').
2. SHEET A-4; NOTES: NOTE 3 INDICATES TO 'REFERENCE S DRAWINGS FOR HP, LP, AND SLOPE OF CAST-IN-PLACE CONCRETE. VERIFY WHERE THOSE ARE FOUND ON THE STRUCTURAL DRAWINGS.
3. SHEET S-1; CAST-IN-PLACE CONCRETE: PROVIDE A NOTE INDICATING THE CLASS OF CONCRETE USED FOR THE VARIOUS DESIGN ELEMENTS (FOOTINGS, SLABS, WALLS, ETC.).
4. SHEET S-6; FOUNDATION PLAN NOTES: NOTE 1 INDICATES AN ALLOWABLE BEARING PRESSURE OF 3000 PSF. THE GEOTECHNICAL REPORT (PAGE 9) INDICATES A DESIGN CONTACT STRESS OF 2500 PSF. MAXIMUM. CLARIFY AND REVISE.
5. SHEET S-10: NO STRUCTURAL CALCULATIONS WERE LOCATED FOR THIS STRUCTURE. PROVIDE.
6. SHEET S-10; BUILDING SECTION C: A NOTE BELOW THE FOOTING TABLE INDICATES THE FOOTING WIDTH AND DEPTH INDICATED "REQUIRES WRITTEN APPROVAL FROM THE STRUCTURAL ENGINEER OF RECORD". EXPLAIN.
7. SHEET S-10 (BUILDING SECTION C); SHEET S-11 (FOUNDATION EARTHWORK NOTES): NOTE 1 INDICATES THE FOOTINGS WILL BE A MINIMUM OF 1'-6" BEARING DEPTH, WHILE THE SECTION (FOOTING TABLE) INDICATES A MINIMUM BEARING DEPTH "D" OF 12". CLARIFY.
8. SHEET S-10; FLOOR PLAN: KEY NOTE 21 IS INDICATED IN THE NORTHEAST CORNER OF THE BUILDING. IS THIS NOTE CORRECT AT THAT LOCATION?
9. GENERAL: THE CHEMICAL AREA STRUCTURE (1200 SF) AND THE SECURITY WALL (1082') WERE NOT INCLUDED IN THE ORIGINAL VALUATION. THESE HAVE BEEN ADDED DURING THIS REVIEW.
10. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/01/2014 JASON GREEN ENGINEERING REVIEW Reqs Change Building Plan can not be approved until approval of the DP Package (DP14-0033).
05/06/2014 MICHAEL ST. PAUL ZONING REVIEW Needs Review Approval of DP14-0033 is required.
05/08/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
05/08/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/08/2014 ROBERT SHERRY WATER REVIEW Approved
05/14/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
05/15/2014 AROMERO4 OUT TO CUSTOMER Completed